Combustion air calculator for gas appliances
Enter the size of the room, the gas appliance and its rated load. The calculator gives the room volume, what the guideline asks for and whether it is met.
How the calculator works
Open-flued gas appliances (type B) take their combustion air from the room. Up to 35 kW together, the guideline is a room with a window or door to the outside and at least 4 m³ per kW, an air network with other rooms through openings of at least 150 cm², or an opening to the outside of 150 cm² (or two of 75 cm² each). Over 35 up to 50 kW it needs the opening to the outside, over 50 kW 2 cm² more per kW (German model combustion regulations § 3, here in the Bavarian version).
For gas cookers and hobs (type A) the TRGI names a room over 15 m³ with a window or door to the outside up to 11 kW, over 2 m³ per kW with extract air up to 18 kW. Room-sealed appliances (type C) take their air from outside through the air/flue system.
The calculator checks one room. The editor checks air networks of several rooms, cooker hoods with extract air and the flue across the whole plan. Combustion regulations are state law in Germany; your state may differ.
Guide: gas cooker and gas boiler – room and combustion air
Results are guide values for planning and do not replace professional planning or measuring on site.