Plan plumbing and water pipes – online in 2D and 3D
Last updated: 16 November 2026
Try it right away
Free in the browser; try it without an account. To save, export and share, create a free account.You plan water pipes by first drawing the bathroom, kitchen and utility room with their fixtures and then running a pipe from each connection to the nearest riser: cold, hot and waste water apart, each at its height in the wall, floor or ceiling. In RoomPlanning every network has its colour after the German DIN conventions, waste pipes get their slope, and risers run through all storeys. In 3D the X-ray view shows the pipes through walls and slabs. All figures here and in the editor are guideline values for orientation, not an engineering design.
How to plan water and drains in RoomPlanning
- Rooms and fixtures first. Draw the bathroom, kitchen and plant room and place washbasin, toilet, shower, bath, sink and washing machine from the catalog (Furnishing). The fixtures bring their connections: cold and hot water and the drain at the usual height.
- Add the pipe networks. Under Building services pick the Pipe tool (key I). In the Pipe networks panel on the right, Add standard networks creates cold water, hot water and waste water; add circulation and rain water when you need them.
- Place a riser. With the Riser tool (key Y) you put the stack or rising main in its place, usually in a shaft or a pre-wall. A riser runs through several storeys (Levels); the waste stack is vented above the roof.
- Draw the pipes. Click from connection to connection and on to the riser. The routing (wall, floor, under the ceiling, exposed, in the ground) sets the height, and waste pipes fall with the slope you chose. Enter or a double click ends the pipe.
- Read the hints. Under Hints in the panel you find, for example, drains below the backwater level, too little slope, open connections or a long hot water run without circulation. A click shows the spot on the plan.
- Check in 3D. In the 3D view, switch Building services to X-ray to see every pipe in walls, floors and ceilings.


The step-by-step guide is in the help under Plan water and drains.
To try it out: an old-building flat whose bathroom, guest WC and kitchen are already connected to cold, hot and waste water.

Period apartment
121 m² · 8 rooms
Abbreviations and colours
Plans tell the pipes apart by the abbreviations of EN 806-1 and DIN 1988-100. The standard does not fix colours for drawings; RoomPlanning uses common, print-safe ones.
| Abbreviation | Meaning | Colour on the plan |
|---|---|---|
| PWC | Cold drinking water | Green |
| PWH | Hot drinking water | Red |
| PWH-C | Circulation | Violet, dashed |
| SW | Waste water | Brown |
| RW | Rain water | Blue, dashed |
| – | Vent pipe | Grey, dashed |
Guideline connection heights
Common heights above the finished floor, to the axis. They come from installation instructions; the manufacturer of your fixture always has the final say.
| Fixture | Cold and hot water | Drain |
|---|---|---|
| Washbasin | about 55 cm, hot on the left, cold on the right | about 50 to 55 cm, DN 40 |
| Wall-hung toilet | cistern inside the pre-wall frame | axis about 23 cm, DN 90/100 |
| Shower | mixer about 110 to 120 cm | in the floor, DN 50 |
| Bath | about 15 to 20 cm above the rim | at the foot of the bath, DN 50 |
| Kitchen sink | angle valves about 50 to 55 cm | about 45 to 50 cm, DN 50 |
| Washing machine | appliance valve about 100 to 120 cm | trap about 60 to 90 cm, DN 50 |
Slope, backflow and frost
- Slope. Unvented branch pipes need at least about 1 %, horizontal pipes inside the building at least 0.5 % (DIN 1986-100, guideline). RoomPlanning works out the heights along the flow from the slope you choose.
- Long branch pipe. If an unvented branch is longer than about 4 m or drops more than about 1 m, it needs venting or an air admittance valve.
- Backwater level. The municipality sets it; without a rule it is usually the street surface. Drains below it, in a basement for instance, need a lifting unit with a loop above that level; a backwater valve is allowed only as an exception.
- Frost. Service and garden pipes are laid frost-free, usually 1.20 to 1.50 m deep; your water supplier gives the exact value.
Hot water and the 3-litre rule
At most 3 litres of water should stand in the pipe between the water heater or the circulation and any tap (DVGW W 551). A 16 × 2 multilayer pipe holds about 0.11 litres per metre, so 3 litres are about 26 m; with 20 × 2 it is only about 15 m. If the run is longer, plan a circulation or an instantaneous heater near the tap. RoomPlanning shows the content of every pipe in litres.
Guideline sizes, material list and drainage application
With Premium RoomPlanning works out a size for every pipe as a guideline value: drinking water from the loading units of the taps (DIN EN 806-3, peak flow as in DIN 1988-300 for residential buildings), waste water from the discharge units (Qww = K·√ΣDU, DIN EN 12056-2 and DIN 1986-100). From them come the material list with pipes, fittings, valves, insulation and clamps (also as CSV), the riser diagram for drinking water and drains and the longitudinal section of the ground pipe. The sheet Drainage application puts site plan, floor plan, riser diagram, section and legend together; which documents your municipality asks for is in its drainage statute. Connect water and drainage proposes the pipes of a bathroom or kitchen to the nearest riser automatically.
Common mistakes
- Planning the drains too late. A toilet far from the stack is often possible only at great effort. Plan the bathroom from the riser out.
- Back slope. A waste pipe that rises again somewhere will block. Check the heights at every point.
- Cold water above hot. Cold water belongs below the hot pipes so it does not warm up.
- Basement without backflow protection. A floor drain below the backwater level without a lifting unit can flood the house in heavy rain.
- A pipe through a window. Mind sill and door heights before you run a pipe in a wall with an opening.
Frequently asked questions
May I plan and install my water pipes myself?
You may plan them yourself, and a good plan makes the talk with the installer easier. In Germany, however, only the water supplier or a company listed in the installers' register may build or substantially change a drinking water installation (§ 12 AVBWasserV). RoomPlanning is a planning aid, not a construction design.
Which colour do cold and hot water have on the plan?
Common are green for cold drinking water (PWC), red for hot drinking water (PWH) and violet for the circulation (PWH-C). Waste water is often drawn brown, rain water blue.
How much slope does a waste pipe need?
As a guideline at least 1 % for unvented branch pipes and 0.5 % for horizontal pipes inside the building, that is 1 cm or 0.5 cm per metre. Drains outside the building usually get more.
Do I need a circulation?
In a one- or two-family house it is not required. It pays off when more than about 3 litres stand in the pipe between the cylinder and a tap, otherwise you wait long for hot water. In larger installations it is mandatory.
What is the backwater level?
The height up to which sewage from the public sewer can push back into the house in heavy rain. Usually it is the street surface. Everything below it, such as drains in the basement, needs protection, as a rule a lifting unit.
Does RoomPlanning size the pipes?
Yes, as a guideline value with Premium: drinking water from loading units (DIN EN 806-3), waste water from discharge units (DIN EN 12056-2, DIN 1986-100). The pressure-loss calculation of DIN 1988-300 and the actual sizing stay with your installer. Without Premium you enter the diameters yourself.
Sources
- § 12 AVBWasserV: customer installation (German) – gesetze-im-internet.de
- Service connection room (German) – Baunetz Wissen
- Waste pipes: sizing and nominal sizes (German) – Baunetz Wissen
- Circulation pipe for drinking water (German) – haustechnikdialog
- Backflow protection leaflet (German, PDF) – StEB Köln
- Backflow (German) – Hamburg.de
- Service connection trench sketch (German, PDF) – Berliner Wasserbetriebe
- Annex 8 GEG: insulation of pipes (German) – gesetze-im-internet.de
All figures are guideline values from freely available sources, based on German rules, and do not replace a design by a registered installation company.