Gas cooker and gas boiler: room and combustion air

Last updated: 16 November 2026

Try it right away

Free in the browser; try it without an account. To save, export and share, create a free account.
Start a floor plan

A gas appliance needs air to burn. Whether the room is enough depends on the kind of appliance: open-flued appliances (type B) take the air from the room and need, as a guideline, 4 m³ of room volume per kW of rated output, an air network with other rooms or an opening of 150 cm² to the outside. A gas cooker up to 11 kW needs a room over 15 m³ with a window or door to the outside. A condensing boiler with a concentric air/flue system (type C) takes its air from outside and asks nothing of the room. All figures here are guideline values after the German model combustion regulations and the TRGI, not an approval.

The combustion air calculator works it out for your room.

Planning as a sketch – work only by registered installers (NDAV § 13). Apart from the network operator, only an installer registered with a network operator may work on gas installations. The district chimney sweep certifies the flue before the first start-up.

Gas appliances by type of flue

TypeAir for burningExampleRequirement for the room (guideline)
Afrom the room, no fluegas cooker, hobup to 11 kW over 15 m³, window or door
Bfrom the roomolder boiler, water heater, open gas fire4 m³ per kW, air network or opening outside
Cfrom outside via the fluecondensing boiler, closed gas firenone

Open-flued appliances (type B) up to 35 kW

Up to 35 kW of rated output together, one of three solutions is enough (MFeuV § 3 (1), here in the Bavarian version):

  1. Room volume: the room has a window that opens or a door to the outside and at least 4 m³ per kW.
  2. Air network: the room is joined to other rooms through openings of at least 150 cm², such as doors with vent grilles. Together, the rooms with a connection to the outside have at least 4 m³ per kW. Rooms without a window or door to the outside do not count.
  3. Opening to the outside: a vent with at least 150 cm² free area, or two of 75 cm² each.

Over 35 up to 50 kW the opening of 150 cm² to the outside is always needed, over 50 kW 2 cm² more per kW above 50, on at most two openings. The openings must not be closed or blocked.

Example: a gas boiler in the kitchen

A kitchen measures 3.20 × 2.80 m at 2.50 m room height, so 22.4 m³. An open-flued boiler of 24 kW hangs there. The guideline asks for 24 × 4 = 96 m³. The kitchen alone is not enough. Options:

  • an air network with the living room and the hall through doors with vent grilles (at least 150 cm² each), when kitchen and living room with their windows have at least 96 m³ together;
  • a vent to the outside of 150 cm² in the outside wall;
  • when replacing it, a room-sealed boiler (type C) with a concentric air/flue system that needs no room air.

Gas cooker and hob

Paragraphs 1 and 2 of the combustion regulations do not apply to domestic gas cooking appliances. The TRGI gives as a guideline: up to 11 kW a room over 15 m³ with a door to the outside or a window that opens; some states ask for 20 m³. Over 11 up to 18 kW more than 2 m³ per kW and an extracting cooker hood or a ventilation system. A cooker with four burners has about 7 to 10 kW, with an oven about 3 kW more.

Extract air and open-flued appliances

A cooker hood with extract air, a vented dryer or a ventilation system can pull a negative pressure in the room and draw flue gas from an open-flued boiler back into the home. Then a safety device is needed, such as a window contact switch or a pressure switch (MFeuV § 4 (2)). Recirculating hoods are not affected.

The outlet above the roof

The flue must rise at least 40 cm above the ridge or be at least 1 m away from the roof surface. For room-sealed gas appliances up to 50 kW with a fan, 40 cm above the roof surface is enough (MFeuV § 9 (1)). A flue through the outside wall is an exception, up to 11 kW for heating or 28 kW for hot water (§ 9 (2)).

Checking room and combustion air in RoomPlanning

In RoomPlanning every room with a gas appliance shows its volume, the connected load and whether the guideline is met. You put vents into walls like windows, doors get a vent grille if you want, and you draw the flue from the appliance up through the roof (Plan gas pipes, help Draw gas pipes).

Detached house with building services in 3D, seen from above at an angle, furnished

Detached house with building services

228.1 m² · 17 rooms

Frequently asked questions

How big must the room for a gas boiler be?

For an open-flued boiler (type B) as a guideline 4 m³ per kW, so 96 m³ for 24 kW, or an air network or an opening of 150 cm² to the outside. A room-sealed condensing boiler (type C) takes its air from outside and may hang in small rooms too.

How big must a kitchen with a gas cooker be?

Up to 11 kW rated load, as a guideline over 15 m³, with a window that opens or a door to the outside. Some German states ask for 20 m³.

What is an air network for combustion air?

Rooms joined by openings of at least 150 cm², such as doors with vent grilles. Their volumes count together, but only those of rooms with a window or door to the outside.

May a gas boiler hang in a bathroom?

Room-sealed appliances (type C) yes; open-flued ones only when the combustion air is enough and no extract fan interferes. If in doubt, the installer clears it with the district chimney sweep.

May I cover the vent?

No. Openings for combustion air must not be closed or blocked; grilles must not narrow the free area.