Hot water circulation: when it is needed (3-litre rule)
Last updated: 16 November 2026
Try it right away
Free in the browser; try it without an account. To save, export and share, create a free account.A circulation keeps the hot water in the pipe warm by returning it to the tank through a second pipe. It is needed when more than 3 litres of water stand in the pipe between the water heater (or the circulation) and a tap (3-litre rule, DVGW W 551). In one- and two-family houses the tank counts as a small system: circulation is not required there, but sensible with long runs, so that the water is hot after about 30 seconds (DIN 1988-200).
Worked example: how long may the hot water pipe be?
The content depends on the inner diameter:
| Pipe | Content per metre | 3 l equal |
|---|---|---|
| Multilayer composite 16×2 | 0.113 l | 26 m |
| Multilayer composite 20×2 | 0.201 l | 15 m |
| Multilayer composite 26×3 | 0.314 l | 9.5 m |
| Copper 15×1 | 0.133 l | 22 m |
If a 26×3 pipe runs 6 m from the tank (1.9 l) and then a 20×2 pipe 7 m (1.4 l) to the shower, 3.3 l stand in the pipe: more than 3 l, so a circulation or an instantaneous water heater at the tap.
Temperatures and insulation
In large systems the water leaves the tank at 60 °C and returns in the circulation at no less than 55 °C. Hot water and circulation pipes are insulated after the GModG (formerly GEG), Anlage 8: up to 22 mm inner diameter 20 mm, up to 35 mm 30 mm (λ = 0.035). Cold water is insulated against warming and runs below the hot water.
Planning circulation with RoomPlanning
RoomPlanning works out the content of every pipe to the tap and gives a hint when it is more than 3 l. You draw the circulation as a network of its own back to the tank (Plan water and drains); with Premium RoomPlanning proposes its size and lists pipes and insulation in the material list.

Detached house with building services
228.1 m² · 17 rooms
Frequently asked questions
Is a circulation required in a single-family house?
No, in a one- or two-family house the tank is a small system for which circulation is not required. With more than 3 l to the tap it is recommended all the same, for hygiene and so the water is hot quickly.
What is the 3-litre rule?
At most 3 litres of water should stand in the pipe between the water heater or the circulation and every tap (DVGW W 551).
What can I do instead of a circulation?
Run the pipe shorter and thinner, or put an instantaneous water heater or an under-sink tank at taps far away.
Sources
- Hot water circulation pipe (German) – haustechnikdialog
- DVGW W 551, extract (PDF, German) – tophotel
- Anlage 8 GEG: insulation of pipes (German) – gesetze-im-internet.de
This guide is general information with guideline values and does not replace planning by a registered plumbing contractor.