Hot water circulation: when it is needed (3-litre rule)

Last updated: 16 November 2026

Try it right away

Free in the browser; try it without an account. To save, export and share, create a free account.
Start a floor plan

A circulation keeps the hot water in the pipe warm by returning it to the tank through a second pipe. It is needed when more than 3 litres of water stand in the pipe between the water heater (or the circulation) and a tap (3-litre rule, DVGW W 551). In one- and two-family houses the tank counts as a small system: circulation is not required there, but sensible with long runs, so that the water is hot after about 30 seconds (DIN 1988-200).

Worked example: how long may the hot water pipe be?

The content depends on the inner diameter:

PipeContent per metre3 l equal
Multilayer composite 16×20.113 l26 m
Multilayer composite 20×20.201 l15 m
Multilayer composite 26×30.314 l9.5 m
Copper 15×10.133 l22 m

If a 26×3 pipe runs 6 m from the tank (1.9 l) and then a 20×2 pipe 7 m (1.4 l) to the shower, 3.3 l stand in the pipe: more than 3 l, so a circulation or an instantaneous water heater at the tap.

Temperatures and insulation

In large systems the water leaves the tank at 60 °C and returns in the circulation at no less than 55 °C. Hot water and circulation pipes are insulated after the GModG (formerly GEG), Anlage 8: up to 22 mm inner diameter 20 mm, up to 35 mm 30 mm (λ = 0.035). Cold water is insulated against warming and runs below the hot water.

Planning circulation with RoomPlanning

RoomPlanning works out the content of every pipe to the tap and gives a hint when it is more than 3 l. You draw the circulation as a network of its own back to the tank (Plan water and drains); with Premium RoomPlanning proposes its size and lists pipes and insulation in the material list.

Detached house with building services in 3D, seen from above at an angle, furnished

Detached house with building services

228.1 m² · 17 rooms

Frequently asked questions

Is a circulation required in a single-family house?

No, in a one- or two-family house the tank is a small system for which circulation is not required. With more than 3 l to the tap it is recommended all the same, for hygiene and so the water is hot quickly.

What is the 3-litre rule?

At most 3 litres of water should stand in the pipe between the water heater or the circulation and every tap (DVGW W 551).

What can I do instead of a circulation?

Run the pipe shorter and thinner, or put an instantaneous water heater or an under-sink tank at taps far away.