Smoke alarm rules in Germany: where smoke alarms must go (all 16 states)

Last updated: 16 November 2026

Try it right away

Free in the browser; try it without an account. To save, export and share, create a free account.
Start a floor plan

Smoke alarms are required in all 16 German states, in new builds and in existing homes. In 14 states they belong in bedrooms, children's rooms and halls that escape routes lead through. Berlin and Brandenburg require them in every habitable room except kitchens and in the halls, Saxony in rooms for sleeping and the halls leading to them. An alarm goes on the ceiling, as near the middle of the room as possible and at least 0.5 m from walls, one per room up to about 60 m². All details are guideline values without guarantee; what counts is the current state building code. Other countries have their own rules.

Smoke alarm rules by German state

The table follows the overview by the German consumer organisation Stiftung Warentest (source dated 3 August 2023, read on 16 November 2026). The retrofit deadlines for existing homes have passed everywhere.

StateRequired inRetrofit byLaw
Baden-Württembergbedrooms, children's rooms, halls and stairs on escape routes31 Dec 2014§ 15 (7) LBO
Bavariabedrooms, children's rooms, halls leading to habitable rooms31 Dec 2017Art. 46 (4) BayBO
Berlinall habitable rooms except kitchens, halls on escape routes31 Dec 2020§ 48 (4) BauO Bln
Brandenburgall habitable rooms except kitchens, halls on escape routes31 Dec 2020§ 48 (4) BbgBO
Bremenbedrooms, children's rooms, halls on escape routes31 Dec 2015§ 48 (4) BremLBO
Hamburgbedrooms, children's rooms, halls on escape routes31 Dec 2010§ 45 (6) HBauO
Hessebedrooms, children's rooms, halls on escape routes31 Dec 2014§ 14 HBO
Mecklenburg-Western Pomeraniabedrooms, children's rooms, halls on escape routes31 Dec 2009§ 48 (4) LBauO M-V
Lower Saxonybedrooms, children's rooms, halls on escape routes31 Dec 2015§ 44 (5) NBauO
North Rhine-Westphaliabedrooms, children's rooms, halls on escape routes31 Dec 2016§ 49 (7) BauO NRW
Rhineland-Palatinatebedrooms, children's rooms, halls on escape routesJuly 2012§ 44 (8) LBauO
Saarlandbedrooms, children's rooms, halls on escape routes31 Dec 2016§ 46 (4) LBO
Saxonyrooms for sleeping and the halls leading to them31 Dec 2023§ 47 (4) SächsBO
Saxony-Anhaltbedrooms, children's rooms, halls on escape routes31 Dec 2015§ 47 (4) BauO LSA
Schleswig-Holsteinbedrooms, children's rooms, halls on escape routes31 Dec 2010§ 49 (4) LBO
Thuringiabedrooms, children's rooms, halls on escape routes31 Dec 2018§ 48 (4) ThürBO

Habitable rooms are rooms where people stay for longer: living, dining, bed, children's, work and hobby rooms. Bathrooms, WCs, storerooms, technical and utility rooms are not. A hall needs an alarm when the escape route from one of those rooms leads through it.

Who installs and who maintains

In most states the owner must install them. Keeping them working, that is testing them and replacing batteries, lies in many states with the direct possessor, in a rented flat with the tenant, unless the owner takes it over, for example with a maintenance contract. In Lower Saxony, Saarland and Saxony it is the residents, in Berlin tenants or other users. The details are in your state's law.

Mounting after DIN 14676-1 (guideline values)

The German standard DIN 14676-1 covers planning, installation and maintenance, EN 14604 the devices themselves. Manufacturers and fire brigades give these values in their leaflets:

RuleGuideline
placeon the ceiling, as near the middle of the room as possible
distanceat least 0.5 m from walls, beams and lights
room sizeone alarm per room up to about 60 m²
halls over about 15 mseveral alarms, at most about 15 m apart
distance to the end wallat most about 7.5 m
kitchen and bathroomrather a heat detector (because of steam), not required

The German Q label stands for a 10-year life, a permanently installed battery and a low false-alarm rate. Interconnected radio alarms sound together, which helps in houses with several storeys.

Worked example: a family house on two storeys

A house in North Rhine-Westphalia with living room, kitchen and study on the ground floor and the main bedroom, two children's rooms and the bathroom upstairs:

RoomAlarms under the NRW rulein Berlin or Brandenburg
living roomnot required1
studynot required1
kitchennot requirednot required
ground-floor hallnot required¹1
main bedroom11
children's rooms (two)22
upper-floor hall11
bathroomnot requirednot required
total47

¹ If the escape route from the bedrooms leads down the stairs through the ground-floor hall, an alarm belongs there too. An extra alarm in the living room does no harm anywhere.

Placing smoke alarms in RoomPlanning

In RoomPlanning you choose your German state, and the Smoke alarms section shows for each storey which required rooms lack an alarm. Place smoke alarms puts the missing ones on the ceiling, in the middle and several in long halls. The check also reports alarms closer than 0.5 m to a wall. It is free; RoomPlanning does not check deadlines. How it works is in the help Smoke alarms and on Plan a network.

Period flat with a radio smart home in 3D, seen from above at an angle, furnished

Period flat with a radio smart home

121 m² · 8 rooms

Frequently asked questions

Do the smoke alarm rules apply to single-family houses?

Yes. The rules cover homes in every kind of building, including an owner-occupied single-family house. It is rarely checked, but the alarm protects above all yourself: smoke does not wake you up in your sleep.

Does the kitchen need a smoke alarm?

In no German state is it required there; Berlin and Brandenburg exempt kitchens too. Steam and cooking often set off a smoke alarm there. If you want the kitchen covered, use a heat detector.

Does the living room need a smoke alarm?

In Berlin and Brandenburg yes, as a habitable room. In the other states it is not required as long as nobody sleeps there. It is still a good idea when the way from the bedrooms leads through it, as in an open living area with stairs.

Who has to install smoke alarms in a rented flat?

In most states the owner, that is the landlord. Regular testing is usually the tenant's job unless the landlord takes it over.

How far from the wall must a smoke alarm be?

As a guideline after DIN 14676-1 at least 0.5 m, and as far from beams and lights. Best is the middle of the room.

Sources

The details are guideline values without guarantee and not legal advice; what counts is the current version of the state building code. Read on 16 November 2026:

This guide is general information and not legal advice.