Installation zones
Where cables and conduits may run in the wall: show the installation zones after DIN 18015-3, the sizes of the zones, conduits and boxes in the zones, chases in load-bearing walls and the hints about them.Installation zones are the strips in walls and ceilings where cables and conduits run. Whoever drills later knows where no cable lies. RoomPlanning shows the zones after the German standard DIN 18015-3 on the floor plan and in the wall view and checks your conduits against them. Try it on the template Detached house with basement; it has a complete conduit network.
Open the template in the editorShow the zones
Open the Layers section at the bottom right and switch Installation zones on with the eye; they start switched off. The floor plan then shows the vertical zones beside doors, windows and wall corners and the band at the ceiling. The horizontal zones lie on top of each other, so they show in the wall view: under Drawings → Wall view for a selected wall, under Room elevations for all walls of a room.

- Switch on installation zones
- Zones at the wall
The zones and their sizes
The zones follow DIN 18015-3. In walls, sizes count from the finished floor and the finished ceiling, beside openings from the shell edge.
| Zone | Where | Preferred |
|---|---|---|
| ZW-o | horizontal, 15 to 45 cm below the ceiling | 30 cm below the ceiling |
| ZW-u | horizontal, 15 to 45 cm above the floor | 30 cm above the floor |
| ZW-m | horizontal, 100 to 130 cm above the floor | 115 cm, only with worktops |
| ZS-t, ZS-f | vertical, 10 to 30 cm beside a door or window | 15 cm beside the shell edge |
| ZS-e | vertical, 10 to 30 cm beside the wall corner | 15 cm beside the corner |
| Ceiling | band up to 30 cm wide | at least 20 cm from the wall |
The middle zone ZW-m exists only in rooms with worktops, that is in the kitchen and the utility room. With single doors the vertical zone lies on the lock side. The outside of exterior walls has its own sizes: horizontally 20 to 40 cm below the ceiling and above the floor, vertically 50 to 70 cm beside the wall edge.
Conduits and boxes in the zones
In the Conduit tool (Plan conduits) you choose the Level: Lower zone and Upper zone put the conduit on the zone's preferred line, Floor lays it on the raw slab, Ceiling at the ceiling. In the wall, conduits run only horizontally or vertically (with Shift).
Boxes may sit outside the zones, a socket at desk height for example. Then you run a vertical stub to it from the nearest horizontal zone. When a conduit ends at a box, this stub comes by itself.
What the hints check
The Hints section of the Conduit tool lists for the zones:
- a conduit in the wall outside the installation zones;
- a box outside the zones without a vertical stub;
- a ceiling conduit closer than 20 cm to a wall.
A click on a hint shows the spot on the plan. Hints block nothing; they are suggestions for the talk with the electrician.
Chases in load-bearing walls
Whether a chase is allowed depends on the wall. Select a wall and set its Structure (masonry, concrete, drywall, timber studs) and whether it is Load-bearing. Left open, RoomPlanning assumes masonry from 11.5 cm, and exterior walls and walls from 17.5 cm as load-bearing. For doors and windows, Own lintel takes the lintel height and bearing; otherwise the guideline of the structure applies. The floor build-up is set on the storey (Floor build-up and heights); it decides how far below the finished floor the structural slab lies.
The hints then check the structure after DIN EN 1996-1-1/NA (tables NA.19 and NA.20, milled):
- horizontal chases only up to 40 cm above or below the structural slab and not too deep;
- vertical chases by depth and width, and their distance to openings;
- conduits through a lintel or its bearing;
- chases in narrow piers or on both faces of the same wall;
- conduits in concrete, drywall and timber.
The chases per wall are also in the bill of materials (Conduit plan and bill of materials).
Good to know
- The zones lie on the Installation zones layer. Under Layers you hide and show them.
- Zones, hints, wall views and room elevations are free.
More guideline values on zones, conduit sizes and fill are under Plan conduits and installation zones.